AWARDED PROJECT


Project Title:   REPAIR ENGINEERING OFFICE SPACE BLD 163/4033/4470
Project Location:   MCAS CHERRY POINT, NC
Contract Number/Solicitation / Project No.:   N40085-10-D-0259/0005  GM16 57556           CCD=09/30/11  $800/DAY LD'S
Program:   GENERAL MACC 

BID SHEET: PLANROOM/GM16_ENGINEERING_OFFICE_SPACE_BLD163_CP/BID SHEET.pdf
DRAWINGS: PLANROOM/GM16_ENGINEERING_OFFICE_SPACE_BLD163_CP/FULL SET DWGS.pdf
SPECIFICATIONS: PLANROOM/GM16_ENGINEERING_OFFICE_SPACE_BLD163_CP/scope.pdf
AMENDMENT 01 clarifications:: PLANROOM/GM16_ENGINEERING_OFFICE_SPACE_BLD163_CP/amen01.pdf
AMENDMENT 02 ANSWERED RFI'S: PLANROOM/GM16_ENGINEERING_OFFICE_SPACE_BLD163_CP/amen02.pdf
AMENDMENT 02 AS BUILT DRAWING FP-1.1 PLANROOM/GM16_ENGINEERING_OFFICE_SPACE_BLD163_CP/Amendment2-Dwg.pdf
AMENDMENT 02 AS BUILT DRAWING: PLANROOM/GM16_ENGINEERING_OFFICE_SPACE_BLD163_CP/Amendment2-As-Built Drawing.pdf
ANSWERED RFI left out of Amendment 02: The following RFI was omitted from the list of questions issued in AMEN 02.  Please see below:

1) Building 163,
The drawings show no Mechanical work required in Zones 4-A, B, C, Zone 5-A and Zone 6. The drawings show work for Zone 5-B only, could you please confirm.

This statement accurately depicts the intentions of the Government. No mechanical work is required in Bldg. 163 with the exception of Zone 5B (as noted).
(Note: There is a thermostat identified in the electrical plans to be relocated within Zone 5A (Sheet 6 of 8-Rev.A).)

Electricians please review and include in your bid:  The electrician is  responsible for providing all the electrical components except the outlet boxes. They will also be responsible for providing the ceiling junction box, running the electrical from the ceiling, through the tile frames and connecting the power/data. Each tile frame pop’s out which will provide easy access to electrical. SEE TWO FILES BELOW:
4033 DIRTT WALLS  LAYOUTS PLANROOM/GM16_ENGINEERING_OFFICE_SPACE_BLD163_CP/furniture layout/FRC Building 4033 DIRTT layouts.pdf
4470  DIRRT WALLS LAYOUT PLANROOM/GM16_ENGINEERING_OFFICE_SPACE_BLD163_CP/furniture layout/FRC Building 4470 DIRTT Walls layout (5-2-11).pdf
3D PRESENTATION: PLANROOM/GM16_ENGINEERING_OFFICE_SPACE_BLD163_CP/furniture layout/FRC Building 4033 DIRTT Wall 3D Presentation.pdf
  